![[Pasted image 20261114211342.png|center]]
- Sys. curve comes from EBE (see pg. 40)
- Sys. curve increase over time due to erosion,... (head reqd. increases) while pump curve decreases due to wear,... -> known as "fouling"
![[Pasted image 20261114211426.png|center|850]]
- After stable point, $H_{sys}>H_{pump}\implies Q\downarrow,$ drift back to operating point
- Before unstable, $H_{pump}>H_{sys}\implies Q\uparrow$ then drift rightward
- For flat pump/sys. curves, driving potential is small so it takes a long time to get back to operating point (unpredictable)
- For
gt;2$ OPs, may oscillate between points (unpredictable)
---
Operating point eqn. given by $H=H_{s}+BQ^2$
where
- static head $H_{s}$ is the elevation difference the pump must overcome even when flow is zero
- system resistance coefficient $B$ represents how strongly increases with flow rate.
To find $B,$ set $BQ^2=H_{L,minor}:$
$
BQ^2=\sum _{\forall\text{ losses}} K_{i} \frac{\bar{V}_{i}^2}{2g}=\sum_{\forall\text{ losses}}K_{i} \frac{Q^2}{2gA^2}
$